Exam 29: Service-Entrance Calculations

arrow
  • Select Tags
search iconSearch Question
  • Select Tags

It is not within the realm of local authorities to publish code requirements specifically for their communities.

Free
(True/False)
4.8/5
(82)
Correct Answer:
Verified

False

When calculating the size of the required service, household cooking equipment demand factors are given in Table ____________________.

Free
(Short Answer)
4.9/5
(83)
Correct Answer:
Verified

220.55

The grounding electrode conductor is sized according to Table ____________________.

Free
(Short Answer)
4.8/5
(82)
Correct Answer:
Verified

250.66

Loads, such as heating and air-conditioning, that do not operate at the same time are said to be non-coincident loads. While separate circuits must be designed to serve each load, when calculating service load per NEC 220.60, only the ____________________ of two non-coincident loads need to be included.

(Short Answer)
4.9/5
(79)

A residence is supplied by 2/0 AWG service entrance conductors. Checking Table 250.66, we find that the minimum grounding electrode conductor must be a(n) ____________________ AWG copper conductor.

(Short Answer)
4.8/5
(64)

When there are four or more appliances fastened in place, a demand factor of ____________________ shall be applied to the appliances.

(Short Answer)
4.9/5
(91)

When figuring kitchen load to calculate residential service size, which of the following must be located?

(Multiple Choice)
4.8/5
(87)

The service neutral conductor may be insulated or bare.

(True/False)
4.8/5
(81)

Where raceways are installed in wet locations above grade, the interior of these raceways shall be considered to be a wet location.

(True/False)
4.8/5
(92)

Sizing the neutral conductor only for the normal neutral unbalance current could result in a neutral conductor too ____ to safely carry fault currents.

(Multiple Choice)
4.8/5
(74)

In a residential service, the grounded (neutral) conductor is permitted to be smaller than the ungrounded (hot) conductors provided it is sized to handle the neutral load and is not smaller than the ____________________.

(Short Answer)
4.8/5
(82)

The main service disconnecting means in this residence is rated ____ amperes.

(Multiple Choice)
5.0/5
(78)

A rather recent innovation for residential metering is "____" metering, also referred to as "real-time" or "smart" metering.

(Multiple Choice)
4.8/5
(83)

When calculating the size of the required service, household electric clothes dryer demand factors are given in Table ____________________.

(Short Answer)
4.8/5
(81)

Table ____________________ may only be used for 120/240-volt, 3-wire, residential single-phase service-entrance conductors, underground service conductors, and feeder conductors that serve as the main power feeder to a dwelling unit.

(Short Answer)
4.8/5
(69)

When calculating residential service load, ____ are allowed for each branch circuit serving laundry receptacles.

(Multiple Choice)
4.8/5
(80)

In addition to carrying the unbalanced current, the service neutral conductor must also be capable of safely carrying any ____________________ that it might be called upon to carry.

(Short Answer)
4.7/5
(87)