Although two-wire cables, such as Type NM and Type AC, contain one black and one white insulated conductor, they are frequently used in residential wiring to supply 240-volt loads. Explain how this can be permitted.

Free
(Essay)
5.0/5
(80)
Correct Answer:
Verified

NEC 200.7(C) allows a white wire to be used as an ungrounded (hot) conductor so long as it is permanently reidentified at all points where connections are made or where it is visible and accessible. Black paint or tape are normally used to mark a white conductor.

The NEC permits flexible cords to be used to supply appliances where ____.

Free
(Multiple Choice)
4.9/5
(93)
Correct Answer:
Verified

D

When making a calculation for sizing a service or feeder, you must include 125 percent of the rating of the total connected fixed space heating load.

Free
(True/False)
4.7/5
(81)
Correct Answer:
Verified

False

The disconnect for motor-driven appliances having a motor of greater than ____ must be within sight of the appliance.

(Multiple Choice)
4.7/5
(97)

The air-conditioner load shall not exceed ____________________ percent of the branch-circuit ampacity if other loads are also served.

(Short Answer)
4.9/5
(75)

For ease of identification, NEC 424.35 requires that leads on heating cables be color-coded. Match the voltages below with the required colors. -240 volts

(Multiple Choice)
4.8/5
(88)

The article that covers cord-and-plug connected air conditioners is ____.

(Multiple Choice)
4.8/5
(81)

Explain the reason that baseboard heating manufacturers do not permit their baseboard heaters to be installed below wall receptacle outlets.

(Essay)
4.8/5
(76)

Baseboard heating units can be controlled by ____.

(Multiple Choice)
4.8/5
(72)

The maximum current and voltage rating permitted by Code for a cord-and-plug connected air-conditioner is ______________________________ at 250 volts.

(Short Answer)
4.8/5
(75)

When Class 2 control wiring is used with central heating and air-conditioning equipment, what is the Code section that prohibits running Class 2 wiring in the same raceway as power conductors?

(Short Answer)
4.9/5
(64)

The total load of an air conditioner shall not exceed ____ percent of the rating of a branch circuit that also supplies lighting.

(Multiple Choice)
4.8/5
(83)

NEC 422.12 on central heating equipment requires that ____.

(Multiple Choice)
4.9/5
(75)

Explain how NEC 422.11 affects selection of branch circuit conductors for appliances, including electric furnaces.

(Essay)
4.8/5
(72)

The total load of an air conditioner shall not exceed ____ percent of the rating of a separate branch circuit.

(Multiple Choice)
4.8/5
(68)

List at least three advantages of electric heating as compared to other types of residential heating systems.

(Essay)
4.9/5
(73)

For ease of identification, NEC 424.35 requires that leads on heating cables be color-coded. Match the voltages below with the required colors. -120 volts

(Multiple Choice)
4.9/5
(75)

Match the following abbreviations used for current values associated with HVAC (heating, ventilating, and air-conditioning) equipment with their meanings. -BCSC

(Multiple Choice)
4.9/5
(80)

For ease of identification, NEC 424.35 requires that leads on heating cables be color-coded. Match the voltages below with the required colors. -480 volts

(Multiple Choice)
4.8/5
(91)

Explain what the NEC requires for a white wire used as an ungrounded (hot) conductor.

(Essay)
4.7/5