What is an effective ground-fault current path?

Free
(Essay)
4.9/5
(79)
Correct Answer:
Verified

​
An effective ground-fault current path is an intentionally constructed, low-impedance electrically conductive path designed and intended to carry current under ground-fault conditions from the point of a ground fault on a wiring system to the electrical supply source and that facilitates the operation of the overcurrent protective device or ground-fault detectors on high-impedance grounded systems. If and when a ground fault occurs, we want the overcurrent device ahead of the ground fault to open as fast as possible to clear the fault. To accomplish this, the integrity of the ground fault current path must be unquestionable.

The ____ is defined in NEC Article 100 as the point of connection between the facilities of the serving utility and the premises wiring .

Free
(Multiple Choice)
4.8/5
(77)
Correct Answer:
Verified

C

What liquid was used in the past in liquid-filled transformers? Is it still in use?

Free
(Essay)
4.8/5
(78)
Correct Answer:
Verified

Years ago, the most widely used liquid was askarel, a mixture of polychlorinated-biphenyls (PCBs)and trichlorobenzene-found to be highly toxic. Askarel was good for indoor installations because it was not flammable, it had excellent insulating characteristics and cooling features, and the cost was attractive. The Toxic Substance Control Act of 1976 and further regulations set forth by the Environmental Protection Agency (EPA)pretty much made askarel a thing of the past. These older transformers have either been replaced over the years or have had the askarel (the PCB liquid)removed and then replaced with noncontaminating liquids.

The lower (or shorter)the ____ of the grounding path, the greater the ground-fault current.

(Multiple Choice)
4.9/5
(75)

Utilities make up the connections on the line side and load side of their transformers according to the ____ requirements.

(Multiple Choice)
4.7/5
(89)

The temperatures of an electrical arc, such as might occur on a 480/277-volt solidly grounded, wye-connected system, are ____.

(Multiple Choice)
4.8/5
(85)

GFPE monitors are designed to sense ____ faults only.

(Multiple Choice)
4.9/5
(80)

The ____ connection scheme has the advantage of being able to provide either 3-phase or 3-phase and single-phase power using only two transformers.

(Multiple Choice)
4.9/5
(89)

In this country and throughout the world, ____ is(are)the common reference point for all electrical systems.

(Multiple Choice)
4.9/5
(76)

When and how does primary high-voltage metering take place?

(Essay)
4.8/5
(72)

____ occur when an ungrounded "hot" conductor comes in contact with a grounded surface or grounded equipment.

(Multiple Choice)
5.0/5
(66)

When is ground-fault protection of equipment not required?

(Essay)
4.9/5
(83)

GFCI protection can be attained using GFCI circuit breakers or GFCI ____.

(Multiple Choice)
4.9/5
(92)

NEC 230.71 permits not more than ____ disconnects to serve as the building disconnecting means.

(Multiple Choice)
4.7/5
(67)

The two basic methods of metering are primary high-voltage metering and ____.

(Multiple Choice)
4.9/5
(75)

NEC 250.64(C)states that grounding electrode conductors generally are not permitted to be ____.

(Multiple Choice)
4.9/5
(84)

Today's liquid-filled transformers have their windings immersed in highly refined mineral oil (combustible), silicone fluid, edible seed oil-based dielectric coolant, or other acceptable nontoxic liquids that have ____ properties.

(Multiple Choice)
4.8/5
(73)

What are the advantages of proper bonding and grounding?

(Essay)
4.8/5
(77)

Dry-type transformers are widely used because they are ____ than comparably rated liquid-filled transformers.

(Multiple Choice)
4.8/5
(68)

NEC 110.16 has a requirement for placing a notice on certain equipment to warn qualified persons of the serious hazard of ____ flash events.

(Multiple Choice)
4.8/5
(71)