Question 181
Multiple Choice
You have the responsibility of designing a railroad track crossing for an outside plant OSP cable. There are three separate railroad tracks to be crossed. The measurement between the center of the two outer tracks is 16 m (52 ft) . Using the standard track width of 1435 mm (4 ft 8.5 in) , what is the length of the rigid steel conduit required to facilitate the crossing?
Question 182
Multiple Choice
What is the insertion loss guideline for a multimode mechanical splice?
Question 183
Multiple Choice
A backbone star topology shall have no more than______ level(s) of cross-connections.
Question 184
Multiple Choice
When balanced twisted-pair copper cabling, return loss is a measurement of the:
Question 185
Multiple Choice
The potential for ______ occurs when devices or systems share a common electromagnetic environment and their operational frequencies overlap.
Question 186
Multiple Choice
A furniture cluster with 26 requires a MINIMUM of how many multiuser telecommunications outlet assembly (MUTOA) ?
Question 187
Multiple Choice
What type of optical fiber is used primarily for outside plant (OSP) applications?
Question 188
Multiple Choice
The ITU-T G.711 standard deals with what aspect of video conferencing?
Question 189
Multiple Choice
The average power consumption in a telecommunications room (TR) is 2260 watts per hour. What is the heat dissipation in BTUs?
Question 190
Multiple Choice
Exhibit:
This diagram illustrates a ______________campus backbone design.
Question 191
Multiple Choice
What is the worst case acceptance value for attenuation when testing 2000 m (6562 ft) of 50/125 multimode fiber at a wavelength of 1300 nm when the fiber has 2 connector pairs and 3 splices?
Question 192
Multiple Choice
It is important to keep all underfloor cabling systems very neat and orderly. Cabling systems must be managed to ensure that air flow is not impeded by the height or volume of underfloor cabling. Keeping copper communications cabling properly separated from is one design approach. To resolve this:
Question 193
Multiple Choice
All of the following are considered market or regional conditions that can impact construction costs EXCEPT:
Question 194
Multiple Choice
If you have a data center where the entire infrastructure must be completely shutdown on an annual basis to perform preventative maintenance and repair work, what tier level would this represent?
Question 195
Multiple Choice
What is the MINIMUM number of outside building terminal pedestals required to serve a single story office, or office warehouse structure that has ten 18.3 m x 24 m (60 ft x 80 ft) units and the total building length is 183 m (600 ft) ?
Question 196
Multiple Choice
What are the three typical voltages used in centrally amplified paging systems?
Question 197
Multiple Choice
What type of redundancy provides two complete units, modules, paths or systems for every one required for a base system.
Question 198
Multiple Choice
The recommended MINIMUM number of conduits connecting two located on the same floor is:
Question 199
Multiple Choice
In a run requiring 15 m (50 ft) of cable between the floor distributor and the consolidation point, the MAXIMUM length of cable allowed between the CP and the telecommunications outlet is:
Question 200
Multiple Choice
On a survey of one of your client's buildings, you discover that one of the TRs, housing a considerable quantity of switching equipment, is at 25 degrees C (77 degrees F) with a relative humidity of 59 percent. This is considered to be: